LAN 63 Supervision panel - Master Unit

 

Technical description
LAN 63 Master Unit with 2 priority outputs and 12 inputs.
When more than 12 inputs are required the LAN 63 is easily expanded with a maximum number of 8 slave modules LAN 64 resulting in an impressive 108 inputs.
Active Input signals lights, after the selected delay time, the channel LED in flashing mode. Tha associated priority output changes state and the priority LED is activated (the acoustic alarm are switched on - LAN 63S).
When the input is acknowledged by the operator, the priority output returns to its original state, the priority LED is deactivated and the channel indicator stops flashing (the acoustic alarm are switched off - LAN 63S).
The channel indicator is activated until the input signal has returned to normal state. A new active signal on any input repeats this process.
When an active input signal triggers the unit but disappears before being acknowledged, the channel indicator remains flashing until being acknowledged after which it is deactivated.
Every input is individually programmable for NO or NC operation, which enables the unit to simultaneously operate with a mixture of NO or NC sensors.
Every input channel has its own programmable delay time in 12 exact steps: 1, 5, 10, 20, 30, 60, 120, 180, 240, 300 seconds and 30 or 60 minutes. Easy connection of additional slave panels through flat cable-connector permanently mounted on LAN 64.

Normal / Idle
Green POWER LED active indicating supply voltage.

Lamp test (LED)
When the TEST/RESET button is held depressed all indicators are activated for inspection.

Inputs 12
Priority outputs 2
Inputs Alarm at closing or opening contact < 1000 Ohm
Indicators Red or yellow LED for input Indicators
Red for priority output A and B
Green LED active indicating supply voltage
Wiring for input sensors 2 wire, max 100m for 0,5 mm² wire. Installed remotely from main cables.
Supply voltage 24 V AC/DC -10% - +20%
Power consumption Operation 40 mA, alarm 95 mA max
Priority / Sum output Changeover relay
Contact rating 1 A at 28 V AC/DC
Input activation current 3 mA
Hole fitting H = 122,2 mm, B = 1 panel 65,0 mm, 2 panels 146,0 mm, 3 panels 227,6 mm
Temperature range -20°C....+50°C
Protection class IP32
Weight 0,12 kg
Tariff No. 8531103000
UNSPSC Code 39121106
Measurements & Variants
 
Information
 
Downloads

Supervision panel LAN 63 features

  • Programmable for Supervision or as Status indicator
  • Compact measurements 129 x 70 x 27 mm (depth below panel 20mm )
  • 12 Inputs
  • Programmable delay individually selectable on each input Max.time 60mins.
  • LED - indicators
  • Noise rejecting inputs
  • Memory and flash function on each input
  • Each input is programmable for NO or NC function and priority output A or B
  • Easily accessible push button switches for RESET and LED-test
  • Potential free priority outputs with NC status when the panel is dienergized
E-number Article no. Description Pcs/pack
6390202 LAN 63 Supervision panel - Master Unit 12 inputs 1
6390237 LAN 63S Supervision panel - Master Unit 12 inputs with buzzer 1
 
Rutab AB (HQ Sweden)
Lerbacksgatan 2
SE-571 38 Nässjö
Sweden

Tel: +46 (0) 380 55 50 50
Fax: +46 (0) 380 123 03
Rutab AB
P.O. Box 11024
SE-100 61 Stockholm
Sweden

Visitor´s:
Malmgårdsvägen 63B
Fax: +46 (0) 8 557 730 05
Rutab AB
Florettgatan 12
SE-254 67 Helsingborg
Sweden
Rutab AS (HQ Norway)
C/O Maxeta AS
Amtmand Aallsgate 89
NO-3716 Skien
Norway

Tel: +47 35595556
Fax: +47 21075559
   
AAA – Highest credit
worthiness